TM 55-1945-205-10-2
0034 00 2
0034 00
2. Position main breaker (3) to the off position.
3. Position all lamp switches (4, 5, 6, 7), to the off (down) position.
CAUTION
Do not use ether in conjunction with the glow plug preheat system. Failure to comply
will result in engine damage.
4. Turn rotary switch (8) to PREHEAT for 5 seconds prior to starting.
CAUTION
Do not crank for more than 15 seconds without allowing starter to cool for
30 seconds. Failure to comply could result in starter damage.
5. Immediately turn rotary switch (8) to START. If engine fails to start, contact unit maintenance.
CAUTION
Keep side doors closed for optimum cooling of unit while running. Failure to comply
could result in engine damage.
6. Release rotary switch (8) after engine continues to run.
NOTE
Allow engine to warm-up for 3 to 5 minute before lamp switches (4, 5, 6, 7) and receptacles
(1 and 2) can be used.
7. If engine stops unexpectedly, refer to troubleshooting procedures. (WP 0100 00)
8. Plug external loads into receptacles (1and 2).
9. Position main breaker (3) to the on position.
10. Position lamp switches (4, 5, 6, 7) to the on positions, as required.