MANUAL OPERATION OF TACTICAL QUIET GENERATOR FIRE SUPPRESSION SYSTEM

TM-55-1945-205-10-2 Water Purification Barges NSN (1930-01-234-2165) Volume 9-3 Electric Power System Manual
Page Navigation
  276    277    278    279    280  281  282    283    284    285    286  
TM 55-1945-205-10-2 0055 00 1 0055 00 OPERATOR MAINTENANCE ROLL-ON/ROLL-OFF DISCHARGE FACILITY GENERATOR CONTAINER OPERATION UNDER UNUSUAL CONDITIONS INITIAL SETUP: Personnel Required Seaman 88K EMERGENCY PROCEDURE - MANUAL OPERATION OF TACTICAL QUIET GENERATOR FIRE SUPPRESSION SYSTEM ACTIVATE FIRE SUPPRESSION SYSTEM WITH ELECTRIC MANUAL PULL :,1* Fire in protected compartments or accidental activation of the CO2 system while personnel occupy compartment could result in serious injury or death to personnel if CO2 is released. Do not depress fire suppression control head lever during normal maintenance. Serious injury or death to personnel could result if CO2 is inhaled. Prior to entering the shelter after discharge of CO2, the shelter shall be completely cleared of any CO2 that may remain. Serious injury or death to personnel could result if CO2 is inhaled. 1. Locate pull station. 1 2 3