TM 55-1945-205-24-2
0084 00 1
0084 00
DIRECT SUPPORT MAINTENANCE
ROLL-ON/ROLL-OFF DISCHARGE FACILITY
GENERATOR CONTAINER OUTLET BOX
REPLACEMENT
INITIAL SETUP:
Tools
Tool Kit, General Mechanics (Item 81, WP 0359 00)
Materials/Parts
Conduit, Outlet
(81703)
NSN 5975-01-064-6415
PN 30203
Personnel Required
Engineer 88L
Equipment Condition
Generator Shut Down. (TM 9-6115-642-10, TM 9-6115-643-10)
Generator Container Hospital Grade Straight Blade Electrical Receptacle Removed. (WP 0082 00)
Generator Container Ground Fault Circuit Interrupter Receptacle Removed. (WP 0083 00)
REMOVE GENERATOR CONTAINER OUTLET BOX
1.
Remove two screws (1) and clamp (2) from strain relief (3).
2.
Pull wiring harness (4) out through strain relief (3).
3.
Remove spanner nut (5) from strain relief (3).
4.
Remove strain relief (3) from junction box (6).
5.
Remove two screws (7) securing junction box (6) to bulkhead. Discard junction box (6).
1
2
5
7
6
3
4