TM 55-1945-205-10-40078 00 1/2 blank 0078 00OPERATOR MAINTENANCEFLOATING CAUSEWAYPERSONNEL SHELTERTROUBLESHOOTING PROCEDURESINITIAL SETUP:Personnel RequiredSeaman 88KTROUBLESHOOTING PROCEDUREFAN DOES NOT OPERATE CONTINUOUSLY WHEN ELECTRICAL POWER IS SUPPLIED TO PERSONNEL SHELTERSYMPTOMFan does not operate continuously when electrical power is supplied to personnel shelter.MALFUNCTIONPower switch on the heating and air conditioning unit is not turned on.CORRECTIVE ACTIONTurn on power switch on unit. (WP 0007 00)Perform operational check of heating and air conditioning system. (WP 0029 00)MALFUNCTIONHeating and cooling circuit breaker is not engaged on personnel shelter electrical distributionpanel board.CORRECTIVE ACTIONEngage heating and cooling circuit breaker on the circuit breaker panel. (WP 0007 00)Perform operational check of heating and air conditioning system. (WP 0029 00)MALFUNCTIONNo power applied to the heating and air conditioning system.CORRECTIVE ACTIONCheck the external shore tie connection from the generator container to the personnel shelter.Perform operational check of heating and air conditioning system. (WP 0029 00)If connection is mated properly, contact unit maintenance.END OF WORK PACKAGE