TM 55-1945-205-10-4
0099 00 31
0099 00
3
After
.4
Generator Container
(Contd)
3. Perform PMCS on generator.
(TM 9-6115-642-10)
4. Clean generator container.
a. Clean the exterior of the
shelter with clean water.
b. Clean the interior floor with a
mop and clean water.
c. Clean the fire suppression
system components with a clean
dry wiping rag.
4
After
.1
Personnel Shelter
1. Check exterior of container
for damage. If damage is found,
contact unit maintenance.
2. Inspect portable fire extinguishers
for broken seal, damage to nozzle or
RED zone indication on gage. If
broken seal, damaged nozzle or
RED zone indication on gage is
found, contact unit maintenance.
Fire extinguisher
is inoperative.
3. Clean the personnel shelter.
a. Clean the VHF/FM handheld
transceivers with a soft bristled
brush to remove all dirt
b. Clean surface of heating and
air conditioning unit with a
wiping rag.
c. Clean benches and table with
clean water.
Table 1. Preventive Maintenance Checks and Services. (Continued)
ITEM
NO.
INTERVAL
MAN-
HOURS
ITEM TO BE
CHECKED OR
SERVICED
PROCEDURE
EQUIPMENT
NOT READY/
AVAILABLE IF: