INSTALL GENERATOR CONTAINER GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLE
INSTALL GENERATOR CONTAINER OUTLET BOX - TM-55-1945-205-24-4_266
TM-55-1945-205-24-4 Modular Causeway System (MCS) Floating Causeway FC-1 NSN 1945-01-473-2162 Manual
Page Navigation
194
195
196
197
198
199
200
201
202
203
204
TM 55-1945-205-24-4
0081 00 1
0081 00
DIRECT SUPPORT MAINTENANCE
FLOATING CAUSEWAY
GENERATOR CONTAINER OUTLET BOX
REPLACEMENT
INITIAL SETUP:
Tools
Tool Kit, General Mechanic’s (Item 53, WP 0253 00)
Materials/Parts
Conduit, Outlet
(81703)
NSN
5975-01-064-6415
PN 30203
Personnel Required
Engineer 88L
Equipment Condition
Generator
Shut Down. (TM 9-6115-642-10, TM 9-6115-643-10)
Hospital Grade Straight Blade Electrical Receptacle Removed. (WP 0079 00)
Ground Fault Circuit Interrupter Receptacle Removed. (WP 0080 00)
REMOVE
GENERATOR
CONTAINER OUTLET BOX
1.
Remove two screws (1) and clamp (2) from strain relief (3).
2.
Pull wiring harness (4) out through strain relief (3).
3.
Remove spanner nut (5) from strain relief (3).
4.
Remove strain relief (3) from
junction box
(6).
5.
Remove two screws (7) securing
junction box
(6) to bulkhead.
6.
Discard junction box (6).
1
2
5
7
6
3