OPERATOR MAINTENANCE
FLOATING CAUSEWAY
GENERATOR CONTAINER FIRE SUPPRESSION SYSTEM
OPERATIONS UNDER UNUSUAL CONDITIONS
INITIAL SETUP:
Tools
Life Preserver, Vest (Item 31, WP 0104 00)
Gloves, Mens and (Leather Palm) (Item 23, WP 0104 00)
Goggles, Sun, Wind and Dust (safety) (Item 25, WP 0104 00)
Helmet, Safety (Item 27, WP 0104 00)
Plug, Ear (Item 41, WP 0104 00)
Personnel Required
Seaman 88K
EMERGENCY PROCEDURE - MANUAL OPERATION OF TACTICAL QUIET GENERATOR FIRE
SUPPRESSION SYSTEM
ACTIVATE FIRE SUPPRESSION SYSTEM WITH ELECTRIC MANUAL PULL
:,1*
All personnel must wear personal flotation device, hard hat, safety shoes and gloves
during FC operations and maintenance. Failure to observe these precautions could
result in serious injury or death.
Fire in protected compartments or accidental activation of the CO2 system while
personnel occupy compartment could result in serious injury or death to personnel
if CO2 is released.
Do not depress fire suppression control head lever during normal maintenance.
Serious injury or death to personnel could result if CO2 is inhaled.
Prior to entering the shelter after discharge of CO2, the shelter shall be completely
cleared of any CO2 that may remain. Serious injury or death to personnel could
result if CO2 is inhaled.
1.
Locate pull station.
127(
A delay of up to thirty seconds will occur before CO2 is discharged.
2.
Lift lever (1) to activate fire suppression system.