TM 55-1945-205-10-4
0090 00 1
0090 00
OPERATOR MAINTENANCE
FLOATING CAUSEWAY
LIGHT TOWER ENGINE
TROUBLESHOOTING PROCEDURES
INITIAL SETUP:
Personnel Required
Seaman 88K
TROUBLESHOOTING PROCEDURE
NO GENERATOR OUTPUT VOLTAGE
SYMPTOM
No generator output voltage.
MALFUNCTION
Main circuit breaker is in the OFF position.
CORRECTIVE ACTION
Turn the main circuit breaker to the ON position. (WP 0032 00)
Perform operational check of light tower. (WP 0032 00)
MALFUNCTION
Receptacle circuit breaker is in the OFF position.
CORRECTIVE ACTION
Use PUSH TO RESET button to restore the receptacle circuit breaker. (WP 0032 00)
Perform operational check of light tower. (WP 0032 00)
MALFUNCTION
Electrical output overload.
CORRECTIVE ACTION
Reduce electrical output. (WP 0032 00)
Perform operational check of light tower. (WP 0032 00)
MALFUNCTION
Loose wire connections.
CORRECTIVE ACTION
Contact unit maintenance.