TM 55-1945-205-24-2
0042 00 1
0042 00
UNIT, DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE
ROLL-ON/ROLL-OFF DISCHARGE FACILITY
GENERATOR CONTAINER
TROUBLESHOOTING PROCEDURES
INITIAL SETUP:
Test Equipment
Multimeter (Item 43, WP 0359 00)
Personnel Required
Engineer 88L
References
TM 55-1945-205-10-2
TROUBLESHOOTING PROCEDURE
DC LIGHTS WILL NOT OPERATE
SYMPTOM
DC lights will not illuminate.
MALFUNCTION
Light bulb(s) burned out.
CORRECTIVE ACTION
Replace light bulb(s). (WP 0089 00)
Perform operational check on DC lighting. (TM 55-1945-205-10-2)
MALFUNCTION
Broken or loose connectors in the DC wiring system.
CORRECTIVE ACTION
Tighten or replace connectors as necessary.
Perform operational check on DC lighting. (TM 55-1945-205-10-2)
MALFUNCTION
DC power source battery appears to be low or discharged.
CORRECTIVE ACTION
Replace battery. (WP 0072 00)
Perform operational check on DC lighting. (TM 55-1945-205-10-2)