TM 55-1945-205-24-2
0110 00 2
0110 00
5.
Set digital multimeter to measure resistance.
NOTE
If readings are infinite, overload protector is defective.
6.
Using digital multimeter, verify resistance between blue START wire (5) and yellow COMMON wire (7) is 3 W.
7.
Using digital multimeter, verify resistance between black RUN wire (4) and yellow COMMON wire (7) is 1 W.
8.
Using digital multimeter, verify resistance between black RUN wire (4) and blue START wire (5) is 4 W.
9.
Connect yellow COMMON wire (7) to indoor thermostat (8) and remove tag.
10. Connect black RUN wire (4) and blue START wire (5) to capacitor (6) and remove tags.
11. Close hinged cover (3) upward.
12. Install two screws (1) to front of control box (2) and tighten.
13. Install heating and air conditioning system side angles. (WP 0103 00)
END OF WORK PACKAGE