UNIT, DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE
FLOATING CAUSEWAY
GENERATOR CONTAINER
TROUBLESHOOTING PROCEDURES
INITIAL SETUP:
Test Equipment
Multimeter (Item 30, WP 0253 00)
Personnel Required
Engineer 88L
References
TM 55-1945-205-10-4
TM 9-6115-642-10
TM 9-6115-643-10
TROUBLESHOOTING PROCEDURE
ELECTRIC FUEL TRANSFER PUMP INOPERATIVE
SYMPTOM
Fuel transfer pump is inoperative.
MALFUNCTION
No power to fuel transfer pump.
CORRECTIVE ACTION
Using a multimeter, verify 24 VDC power to the pump. If present, replace pump.
(TM 9-6115-642-10, TM 9-6115-643-10)
If voltage to the pump is not present, use multimeter to verify continuity of the wiring
between the pump and the circuit breaker panel. If continuity is not present, repair/replace
wiring as necessary. (WP 0248 00)
Perform operational check of electric fuel pump. (TM 55-1945-205-10-4)