TM 55-1945-205-24-4
0107 00 1
0107 00
DIRECT SUPPORT MAINTENANCE
FLOATING CAUSEWAY
HEATING AND AIR CONDITIONING SYSTEM OVERLOAD PROTECTOR
TESTING
INITIAL SETUP:
Test Equipment
Multimeter (Item 30, WP 0253 00)
Tools
Tool Kit, General Mechanics (Item 53, WP 0253 00)
Personnel Required
Utilities Equipment Repairer 52C
Equipment Condition
Heating And Air Conditioning Side Angles Removed. (WP 0100 00)
TEST HEATING AND AIR CONDITIONING SYSTEM OVERLOAD PROTECTOR
1.
Remove two screws (1) from front of control box (2).
2.
Open hinged cover (3) downward.
3.
Tag and disconnect black RUN wire (4) and blue START wire (5) from capacitor (6).
4.
Tag and disconnect yellow COMMON wire (7) from indoor thermostat (8).
5.
Set digital multimeter to measure resistance.
3
6
2
7
8
1
5
4