TM 55-1945-205-24-20026 00 20026 00CORRECTIVE ACTIONClean and replace condensor and coil fins as required. (WP 0109 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-2)MALFUNCTIONCompressor system wiring is defective.CORRECTIVE ACTIONRepair/replace wiring as necessary. (WP 0348 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-2)MALFUNCTIONCompressor system has low voltage running to it.CORRECTIVE ACTIONUsing multimeter, check continuity between compressor motor black wire and other compressor wires. If continuity is not present, repair/replace wiring as necessary. (WP 0348 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-2)MALFUNCTIONThe system overload protector is defective.CORRECTIVE ACTIONTest the overload protector. (WP 0110 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-2)MALFUNCTIONThe system capacitor is defective.CORRECTIVE ACTIONReplace the capacitor. (WP 0111 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-2)