TM 55-1945-205-24-2
0088 00 2
0088 00
2.
Loosen three screws (2).
3.
Pull wires (1) straight out of circuit breaker (3).
4.
Firmly grasp circuit breaker (3) at the midline of the load bank (4), rotate circuit breaker (3) outward and discard.
INSTALL GENERATOR CONTAINER ELECTRICAL DISTRIBUTION PANEL THREE POLE
CIRCUIT BREAKER
1.
Install the back side of the new circuit breaker (3) into mounting cleats (5).
2.
Rotate circuit breaker (3) onto the midline of the load bank (4), until it snaps into position.
WARNING
3.
Coat wires (1) with silicone grease.
4.
Install wires (1) into circuit breaker (3) and remove tags.
5.
Tighten screws (2).
6.
Install generator container electrical distribution panel access cover. (WP 0086 00)
END OF WORK PACKAGE