INSTALL PERSONNEL SHELTER GROUND FAULT CIRCUIT INTERRUPTER (GFCI) RECEPTACLE
INSTALL PERSONNEL SHELTER OUTLET BOX - TM-55-1945-205-24-2_378
TM-55-1945-205-24-2 Modular Causeway System (MCS) Roll-On/Roll-Off Discharge Facility Model (RRDF) RRDF-1 NSN 1945-01-473-2282 Manual
Page Navigation
295
296
297
298
299
300
301
302
303
304
305
TM 55-1945-205-24-2
0126 00 1
0126 00
DIRECT SUPPORT MAINTENANCE
ROLL-ON/ROLL-OFF DISCHARGE FACILITY
PERSONNEL SHELTER OUTLET BOX
REPLACEMENT
INITIAL SETUP:
Tools
Tool Kit, General Mechanic’s (Item 81, WP 0359 00)
Materials/Parts
Conduit, Outlet
(81703)
PN 30203
Personnel Required
Engineer 88L
Equipment Condition
Generator
Shut Down. (TM 9-6115-642-10, TM 9-6115-643-10)
Personnel Shelter Hospital Grade Straight Blade Electrical Receptacle Removed. (WP 0124 00)
Personnel Shelter Ground Fault Circuit Interrupter Receptacle Removed. (WP 0125 00)
REMOVE PERSONNEL SHELTER OUTLET BOX
NOTE
This task is typical for both the hospital grade straight blade and ground fault circuit
interrupter receptacle boxes.
1.
Remove two screws (1) and clamp (2) from each strain relief (3).
2.
Pull wiring harness (4) out through strain relief (3).
3
2
1
5
5
7
6
3
2
1
4
4