TM 55-1945-205-24-4
0120 00 2
0120 00
4.
Remove panel (5) from junction box (4).
a.
Remove four screws (6) securing panel (5) to junction box (4).
b.
Remove panel (5).
5.
Remove terminal block (7) from panel (5).
a.
Remove two screws (8) and nuts (9) securing terminal block (7) to panel (5).
b.
Remove terminal block (7).
6.
Remove relay (10) from relay socket (11).
a.
Remove spring (12) securing relay (10) to relay socket (11).
b.
Remove relay (10) from relay socket (11) by pulling outwards.
7.
Remove relay socket (11) from panel (5).
a.
Remove two screws (13) and nuts (14) securing relay socket (11) to panel (5).
b.
Remove relay socket (11).
8.
Install relay socket (11) on panel (5).
a.
Position relay socket (11) on panel (5).
b.
Install two screws (13) and nuts (14) to secure relay socket (11) to panel (5). Tighten nuts (14).
9.
Install relay (10) in relay socket (11).
a.
Position relay (10) in relay socket (12) by pushing inwards.
b.
Install spring (12) to hold relay (10) in relay socket (11).
10. Install terminal block (7) on panel (5).
a.
Position terminal block (7) on panel (5).
b.
Install two screws (8) and nuts (9) to secure terminal block (7) to panel (5). Tighten nuts (9).
11. Install panel (5) in junction box (4).
a.
Position panel (5) in junction box (4).
b.
Install four screws (6) to secure panel (5) to junction box (4). Tighten screws (6).
12. Connect internal electrical wiring within junction box (4) and remove tags.
13. Close enclosure cover (2) and secure by tightening two screws (3).
14. Position circuit breaker D (1) on the personnel shelter electrical distribution board to ON.
END OF WORK PACKAGE