TM-5-5420-279-10
Table 9. 2 Launch Frame Electrical Control Enclosure MIMIC Panel; Indicator lights
(continued)
Indicator
Light
Notes
Checks of Non Normal Status
Normal
Status
OFF
Indicates a MINOR fault
LOW OIL level signal in an alarm
Minor Fault
with the launcher.
condition for a continuous period for
more than 5 seconds.
OIL TEMP sensor alarm, sensor signal
out of normal operating range of less
than 4mA or more than 20mA for a
continuous period of more than
1 second.
OIL TEMP sensor indicating an oil
temp of more than 158 degrees
Fahrenheit (70 degrees centigrade).
OIL TEMP sensor indicating and oil
temp of less than 32 degrees
Fahrenheit (0 degrees centigrade).
FILTER 1 differential pressure switch
in an alarm condition for a continuous
period of more than 5 seconds (cab
switch must be in position 2 or 4).
FILTER 2 differential pressure switch
in an alarm condition for a continuous
period of more than 5 seconds (cab
switch must be in position 2 or 4).
continued
9-13