TM 55-1945-205-10-4
0026 00 2
0026 00
:,1*
Ensure container, generator and fuel nozzle are grounded before beginning
refueling operation. Failure to observe these precautions could result in serious
injury or death.
&,21
Fuel Level: Fill using CLEAN DIESEL fuel (as required) and at the end of the day to
minimize condensation. Refer to Table 1 for correct diesel fuel for the environment
where equipment is being operated, otherwise damage to equipment could occur.
127(
Fire extinguisher and spill kit must be present during refueling.
2.
Attach fuel nozzle to fill port (1). Procedure is the same for outside or inside fill port.
Table 1. Diesel Fuel.
AMBIENT TEMPERATURE
DIESEL FUEL
+20°F to + 120°F (-7°C to + 49°C)
W-F-800 Grade DF-2 JP4, JP5, JP8
0°F to + 20°F (-17°C to + 7°C)
W-F-800 Grade DF1 JP4, JP5 JP8
-25°F to 0°F (-32°C to -17°C)
W-F-800 Grade DF-1
-25°F to 0°F (-32°C to -17°C)
W-F-800 Grade DF-A
VENT
1