TM 55-1945-205-24-2
0029 00 1
0029 00
UNIT, DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE
ROLL-ON/ROLL-OFF DISCHARGE FACILITY
HEATING AND AIR CONDITIONING SYSTEM
TROUBLESHOOTING PROCEDURES
INITIAL SETUP:
Test Equipment
Multimeter (Item 43, WP 0359 00)
Personnel Required
Engineer 88L
Utilities Equipment Repairer 52C
References
TM 55-1945-205-10-2
TROUBLESHOOTING PROCEDURE
COMPRESSOR WILL NOT START AND MAKES NO NOISE
SYMPTOM
Compressor makes no noise and will not start.
MALFUNCTION
Thermostat is set too high or low.
CORRECTIVE ACTION
Adjust thermostat switch to required setting. (TM 55-1945-205-10-2)
MALFUNCTION
Compressor has no power.
CORRECTIVE ACTION
Position power switch to AUTO, FAN, COOL or HEAT.
Perform operational check on heating and air conditioning system.
(TM 55-1945-205-10-2)
Check that power cord is connected.
Perform operational check on heating and air conditioning system.
(TM 55-1945-205-10-2)
On personnel shelter electrical distribution panel, check circuit breaker A to be sure it is
turned on. (TM 55-1945-205-10-2)
Perform operational check on heating and air conditioning system.
(TM 55-1945-205-10-2)