TM 55-1945-205-24-40026 00 10026 00UNIT, DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCEFLOATING CAUSEWAYHEATING AND AIR CONDITIONING SYSTEMTROUBLESHOOTING PROCEDURESINITIAL SETUP:Test EquipmentMultimeter (Item 30, WP 0253 00)Personnel RequiredEngineer 88LUtilities Equipment Repairer 52CReferencesTM 55-1945-205-10-4TROUBLESHOOTING PROCEDURECOMPRESSOR STARTS AND RUNS, BUT CYCLES ON THE OVERLOADSYMPTOMCompressor runs, but cycles on the overload.MALFUNCTIONIndoor air filter is dirty or plugged.CORRECTIVE ACTIONClean and replace the indoor air filter as required. (WP 0097 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-4)MALFUNCTIONVent air filter is dirty or plugged.CORRECTIVE ACTIONClean and replace the vent air filter as required. (WP 0099 00)Perform operational check on heating and air conditioning system. (TM 55-1945-205-10-4)MALFUNCTIONThe condenser and coil fins are dirty or plugged.