TM 55-1945-205-24-4
0027 00 2
0027 00
MALFUNCTION
The system capacitor is defective.
CORRECTIVE ACTION
Replace the capacitor. (WP 0108 00)
Perform operational test on heating and air conditioning system. (TM 55-1945-205-10-4)
MALFUNCTION
The fan motor is defective.
CORRECTIVE ACTION
Replace fan motor. (WP 0105 00)
Perform operational test on heating and air conditioning system. (TM 55-1945-205-10-4)
MALFUNCTION
The capillary tube and strainer are restricted or plugged.
CORRECTIVE ACTION
Clean or replace the capillary tube and strainer as required. (WP 0103 00)
Perform operational test on heating and air conditioning system. (TM 55-1945-205-10-4)
MALFUNCTION
Air is in the system.
CORRECTIVE ACTION
Service air conditioning system. Contact depot maintenance.
MALFUNCTION
Pressure in the system is not equalized.
CORRECTIVE ACTION
Service the air conditioning system. Contact depot maintenance.
END OF WORK PACKAGE