TM 55-1945-205-24-40003 00 110003 00The CO2 fire suppression system is controlled by the control module. Upon sensing that a fire is present, the control module activates the fire suppression sequence. A time delay between the initial alarm condition and operation of the shutdown relay occurs. This delay may be programmed for 5, 10, 20 or 30 seconds by the user. The shutdown relayshuts down the generator and allows personnel time to vacate the shelter. After the delay sequence is completed, a second delay before actuation of the fire extinguishing agent occurs. This second delay may be programmed for 5, 10, 20 or 30 seconds by the user. When using the manual pull station, the delays used in the automatic mode are implemented by the control module.The shelter is equipped with Alternating Current (AC) fluorescent light fixtures. A load center is used to control the alternating current system. A Direct Current (DC) lighting system, comprised of a spring wound timer switch and light fixtures, supply light when AC lighting is not available.An EMERGENCY STOP button is mounted inside the ISO container personnel access door. When pressed, the EMERGENCY STOP button stops the generator.VENT INTAKE OPENINGWITH MOTOR OPERATEDLOUVERDIESEL EXHAUSTMANUAL FUEL TRANSFER PUMPGENERATOR SETTACTICAL QUIETPOWER CABLE PLUG CONNECTOR120 VAC LOAD CENTERVENT EXHAUST OPENINGWITH MOTOR OPERATEDLOUVERCO2 FIRE SUPPRESSION SYSTEMINTERIOR EMERGENCY STOP SWITCH24 VDC LIGHTING SWITCH W/TIMER1,000 GAL AUXILIARYFUEL TANK (COVERS FLOOR)AUXILIARY FUELTANK FILLPERSONNEL ACCESSDOORSTEPS