The CO2 fire suppression system is controlled by the control module. Upon sensing that a fire is present, the control
module activates the fire suppression sequence. A time delay between the initial alarm condition and operation of the
shutdown relay occurs. This delay may be programmed for 5, 10, 20 or 30 seconds by the user. The shutdown relay
shuts down the generator and allows personnel time to vacate the shelter. After the delay sequence is completed, a
second delay before actuation of the fire extinguishing agent occurs. This second delay may be programmed for
5, 10, 20 or 30 seconds by the user. When using the manual pull station, the delays used in the automatic mode are
implemented by the control module.
The shelter is equipped with Alternating Current (AC) fluorescent light fixtures. A load center is used to control the
alternating current system. A Direct Current (DC) lighting system, comprised of a spring wound timer switch and
light fixtures, supply light when AC lighting is not available.
An EMERGENCY STOP button is mounted inside the ISO container personnel access door. When pressed, the
EMERGENCY STOP button stops the generator.